Using ProLink
®
Software with Micro Motion
®
Transmitters
153
Calibrate Menu
continued
Milliamp output trim
Applications Menu Help Menu
Configure Menu:
Meter Factors
Calibrate Menu Test Menu
Figure 14-14.Milliamp output trim: setting output to 4 mA
2. Choose OK to set the output at the 0 mA or 4 mA level.
3. When the dialog box shown in
Figure 14-14
appears, read the
amount of current indicated by the reference device. The current
level should be approximately 4 mA, regardless of the 0-20 or
4-20 mA span of the output. Enter the measured amount of current
into the Enter Meas Output text box, shown in
Figure 14-15
, then
choose Do Cal.
Figure 14-15.Milliamp output trim: enter measured low output
4. When the Compare Output Trim dialog box appears, choose Yes if
the reference device indicates approximately 4 mA. If the reference
device indicates an output level that is not acceptably close to 4 mA,
choose No, then repeat step 3.
5. When Yes is chosen in step 4, choose OK to set the output at 20 mA.
6. When the dialog box shown in
Figure 14-16
appears, read the
amount of current indicated by the reference device. The current
level should be approximately 20 mA. Enter the measured amount of
current into the Enter Meas Output text box, then choose Do Cal.